Path for Zero Sequence Currents in Transformers & Fault Calculations on a Power System Networks
The main theme of this section is to calculating different sequence components and analysing different symmetrical and unsymmetrical fault calculations.
Summary
The main theme of this section is to calculating different sequence components and analysing different symmetrical and unsymmetrical fault calculations.
Things to Remember
- Positive sequence currents are present in all type of faults.
- Negative sequence currents are present in unsymmetrical faults.
- Zero sequence currents are present when neutral of the system is grounded & fault also involves ground.
MCQs
No MCQs found.
Subjective Questions
No subjective questions found.
Videos
No videos found.

Path for Zero Sequence Currents in Transformers & Fault Calculations on a Power System Networks
Path for Zero Sequence Currents in Transformers:
In transformer positive sequence network and negative sequence impedances are equal. But zero sequence impedances of transformer depend on the connection of the primary and secondary windings and status of the neutral terminal in case of star connected windings.
The different connection type of transformer and its equivalent zero sequence circuits are shown in the figure below. The zero sequence currents path can be determined by using these equivalent zero sequence circuit.
Fault Calculations on a Power System Network:
Line to Ground Faults:
Let us consider a fault occurs between phase a and ground through impedance Zf at bus k of power system network as in fig below.

Conditions, derivation and equivalent sequence circuit is similar as of the single line to ground fault on the terminal of unloaded synchronous generator
Hence, the result is:
Where Zkk(0), Zkk(1) and Zkk(2) are diagonal element at k axis of corresponding bus impedance matrix and Vk(0) is prefault voltage at bus k
The fault current can be determined by using the matrix equation i.e.
Line to Line Faults:
Let us consider a fault occurs between phase a and b through an impedance Zf at bus k of power system network as in fig below.

Conditions, derivation, and equivalent sequence circuit are similar as of the line to line fault on the terminal of unloaded synchronous generator
Hence, the result is:
Where Zkk(0), Zkk(1) and Zkk(2) are diagonal element at k axis of corresponding bus impedance matrix and Vk(0) is pre fault voltage at bus k
The fault current can be determined by using the matrix equation i.e.
Double line to ground fault:
Let us consider a fault occurs between phase a and b through an impedance Zf to the ground at bus k of power system network as in fig below.

Conditions, derivation, and equivalent sequence circuit are similar as of the double line to ground fault on the terminal of unloaded synchronous generator
Hence, the results are:
Where Zkk(0), Zkk(1) and Zkk(2) are diagonal element at k axis of corresponding bus impedance matrix and Vk(0) is prefault voltage at bus k
The fault current can be determined by :
Lesson
Unsymmetrical Faults on Power Systems
Subject
Electrical Engineering
Grade
Engineering
Recent Notes
No recent notes.
Related Notes
No related notes.