Parallel Operation and Synchronization and Infinite Bus Concept

The two alternators are operating in parallel so that the above requirements are satisfied, they are said to be synchronous. The operation of getting the machine into synchronism is known as synchronization and system of constant voltage & constant frequency regardless of load is known as an infinite bus.

Summary

The two alternators are operating in parallel so that the above requirements are satisfied, they are said to be synchronous. The operation of getting the machine into synchronism is known as synchronization and system of constant voltage & constant frequency regardless of load is known as an infinite bus.

Things to Remember

The lamp L1 is connected across R & R1, L2 is connected to Y & B1 & L3 is connected across B & Y1. Physically these three lamps are installed in a triangular format.

MCQs

No MCQs found.

Subjective Questions

No subjective questions found.

Videos

No videos found.

Parallel Operation and Synchronization and Infinite Bus Concept

Parallel Operation and Synchronization and Infinite Bus Concept

Parallel operation and synchronization:

The operation of connecting the alternator in parallel with another alternator or with common bus bar is known as synchronizing.In an actual power system,a number of generators are connected in parallel according to consumers demand. If the load on a generator station becomes so large that the rating of the running generators is exceeded, it becomes necessary to add another generator in parallel to increase the power available from the generating station.For the two or more synchronous generators may be connected in parallel; the following conditions must be fulfilled:

»Their phase sequence must be the same (phase 1 to phase 1 ,phase 2 to phase 2 & phase 3 to phase 3)

»Terminal voltage if both alternators must be equal.

»The waveform of emf generated by both alternator should be in phase.

»The frequency of the both alternator must be equal.

»The percent impedance of both alternators should be same.

fig:Parallel operation of alternators
fig:Parallel operation of alternators

The two alternators are operating in parallel so that the above requirements are satisfied, they are said to be synchronous. The operation of getting the machine into synchronism is known as synchronization.

Above figure shows an arrangement for synchronizing two alternators. M/C A is running & M/C B is required to be connected in parallel with M/C B.

At First,the phase sequence is checked to confirm the respective phases are connected. Phase sequence is checked by phase sequence indicator.

Which is small 3 phase induction motor that rotates in one direction for one phase sequence and in opposite in another phase sequence.

As shown in the figure,M/C Bis rotated by prime mover approximately up to its synchronous speed keeping circuit breaker CB-2 open.Excitation ofM/C B is adjusted so that so that it's generated voltage V2 is same as that of V1.

The lamp L1 is connected across R & R1, L2 is connected to Y & B1 & L3 is connected across B & Y1. Physically these three lamps are installed in a triangular format.

fig:Showing connection of synchronizing lamps
fig:Showing connection of synchronizing lamps

For frequency check,there may be following three cases:

Case I:

When phasors R1, Y1& B1 rotate with the same speed as R,Y & B phasors.

Then, L1 becomes dark.

L2 becomes bright

& L3 becomes bright.

Case II:

When phasors R1, Y1& B1 rotate faster than R,Y & B phasors.

Then,

L1 starts to glow.

Brightness decreases in L2 .

& Brightness increase in L3.

In such a case, the speed of generator G­2 has been reduced until f1 =f2.where L1 is dark and L2 & L3 glow with equal brightness.Then CB-2 is closed.

Case III:

When phasors R1, Y1& B1 rotate slower than R,Y & B phasors.

Then,

L1 starts to glow.

The brightness increases in L2 .

& Brightness decrease in L3.

In such a case,the speed of generator G2 has to be increased until f1=f2.Where, L1 is dark abd L2 & L3 glow with equal brightness.

Hence,The same frequency condition of that alternator can be checked by the three lamps as shown in the figure above.

Operation on Infinite Bus:

The infinite bus system is system behaves like a large generator having virtually zero internal impedance & infinite rotational inertia.Such a system of constant voltage & constant frequency regardless of load.

fig:infinite bus
fig:infinite bus

An alternator connected to an infinite bus have following operating characteristics:

  1. The terminal voltage & frequency of the generator is controlled by the system to which it is connected.
  2. The governor of alternator controlled the real power supplied by the alternator to an infinite bus.
  3. The field current or excitation in alternator controls reactive power supplied by the alternator to an infinite bus.Increasing the field current on alternator operating in parallel with infinite bus increases the reactive power output of the alternator.

fig:Graph of V&f versus Q&P respectively
fig:Graph of V& f versus Q& P respectively

Lesson

Three Phase Synchronous Generator

Subject

Electrical Engineering

Grade

Engineering

Recent Notes

No recent notes.

Related Notes

No related notes.